UPS System Glossary | Resources

24 Jun.,2024

 

UPS System Glossary | Resources

Alpine created this page as a resource for technical terminology relating to UPS systems.

Please visit our website for more information on this topic.

Active redundancy

Parallel UPS configuration in which several UPS units with equal outputs are parallel connected and share the load. In the event one UPS unit fails, the other units pick up its share without any interruption in the supply of power to the load.

Alternate power source

Backup source used in the event of a mains failure. The connection time and the duration of the source depend on the type of source used.

Back-up time

Time during which the UPS can supply the rated load with nominal-quality power while utility power is down. This time depends on the battery and the efficiency of the UPS. Typical backup ranges from five minutes to several hours.

Battery on shelves

Battery cell installation system whereby the cells are placed on several vertically stacked shelves or racks made of insulating material.

Battery (recombination)

Battery with a gas recombination rate at least equal to 95%, i.e. no water need be added over battery life. So, usually called "maintenance free."

Battery (tier-mounted)

Battery cell installation system whereby the cells are placed on tiers made of insulating material.

Battery (vented)

The battery cells are equipped with a filling port for distilled, demineralized water used to top up the free electrolyte.

Battery cells

The interconnected battery elements that supply electrical power created by electrolytic reaction.

Battery circuit breaker

DC circuit breaker that protects the battery of a UPS.

BMS (Building Management System)

System used for control/monitoring building utilities and systems. It is generally composed of sensors, actuators and programmable controllers connected to a central computer or several computers, equipped with specific software.

Bypass

The act of taking the UPS offline and feeding the critical bus from utility power. This can be done either manually, for service, or automatically in the event of failure or overload.

Charger

Device associated with the rectifier and used to supply the battery with the electrical power (DC current) required to recharge and/or float charge the battery

Circuit breaker (battery)

DC circuit breaker that protects the battery of a UPS.

Conductance

The technical description of conductance is the real part of complex admittance. It is a measure of an electrical circuit current response that results when an AC voltage pulse of a known frequency and amplitude is applied. Siemens is the international unit of measure which is sometimes called "MHOS", which of course is Ohms spelled backward. Conductance is also sometimes referred to as "admittance" or "acceptance", because it relates the electrical (conductive) efficiency of a circuit. The conductance value is one way to measure the resistive characteristic of any battery or cell. As batteries age and fail, their internal resistance will typically increase because the plate surface can sulfate or shed active material, which adversely affects its ability to perform. This increase in resistance can be observed with declining conductance readings. It is a measure of that decline over time that can be used to calculate the capacity loss in cell or battery as it occurs. This is done without discharging the cell or battery, and the simple rule of thumb is; high conductance is GOOD, low conductance is typically BAD.

Cos phi

A measure of the phase shift between the current wave and the voltage wave observed at the terminals of a load supplied with AC power at a given frequency.

Cos phi1

A measure of the phase shift between the fundamental current wave and the fundamental voltage wave observed at the terminals of a non-linear load.

Crest factor (Fc)

Ratio between the peak current value to the rms current value.

Current (inrush)

Temporary current observed in a network when electrical devices are energized, generally due to the magnetic circuits of the devices. The effect is measured by the currents maximum peak value and the rms current value it generates.

Current harmonics

All alternating current which is not absolutely sinusoidal is made up of a fundamental and a certain number of current harmonics which are the cause of its deformation (distortion) when compared to the theoretical sine-wave. For each current harmonic of order n and an rms value In, there is a voltage harmonic with an rms value Un. If Zsn is the voltage source output impedance for the harmonic of the nth order, then: Un = Zsn x In

Current loop (20 mA)

Transmission system used on certain devices and offering better performance than the RS232C. It provides a high degree of immunity to interference and is easy to implement, but has not been standardized.

Distortion (individual)

Ratio between the rms value of an nth order harmonic and the rms value of the fundamental.

Distortion (total)

Ratio between the rms value of all harmonics of a non-sinusoidal alternating periodic value and that of the fundamental. This value may also be expressed as a function of the individual distortion of each harmonic Hn = Yn /Y1

Electromagnetic compatibility

Possibility of a device to operate normally when installed near other devices, given the disturbances emitted by each device and their mutual sensitivities.

Filter (phase-shift)

Filter used to reduce, if necessary, the overall distortion due to the current harmonics injected into the utility upstream of a UPS by its rectifier-charger. Filtering is superior to that of a traditional filter of the L or C type.

Floating voltage

DC voltage applied to the battery to maintain its charge level. This voltage depends on the type of battery, the number of cells and the manufacturer ís recommendations.

Fourier theorem

Theorem stating that any non-sinusoidal periodic function (frequency f) may be represented as a sum of terms (series) made up of: n a sinusoidal term with frequency f, called the fundamental frequency, n sinusoidal terms with frequencies that are whole multiples of the fundamental frequency, (harmonics), n a possible DC component where n is a whole number. n = 1 corresponds to the fundamental, n > 1 to the harmonic of the nth order.

Harmonic

Sinusoidal term of the Fourier series expansion of a periodic function. The harmonic (or harmonic component) of the nth order is characterized by: Yn is the rms value of the given harmonic component, w is the angular frequency of the fundamental, related to frequency by : w = 2¼f; phin is the phase angle of the given harmonic component at t = 0.

Harmonics (current and voltage)

All alternating current which is not absolutely sinusoidal is made up of a fundamental and a certain number of current harmonics which are the cause of its deformation (distortion) when compared to the theoretical sine-wave. For each current harmonic of order n and an rms value In, there is a voltage harmonic with an rms value Un. If Zsn is the voltage source output impedance for the harmonic of the nth order, then: Un = Zsn x In

High-frequency interference

High-frequency parasitic current that is either conducted (electrostatic origin) or radiated (electromagnetic origin) by a device.

Individual distortion

Ratio between the rms value of an nth order harmonic and the rms value of the fundamental.

Inrush current

Temporary current observed in a network when electrical devices are energized, generally due to the magnetic circuits of the devices. The effect is measured by the currents maximum peak value and the rms current value it generates.

Interference (high-frequency)

High-frequency parasitic current that is either conducted (electrostatic origin) or radiated (electromagnetic origin) by a device.

Inverter

UPS subassembly that recomposes a sine-wave output (regulated and without breaks) using the DC current supplied by the rectifier-charger or the battery. The primary elements of the inverter are the DC/AC converter, a regulation system and an output filter.

Inverter (off-line or stand-by)

UPS configuration in which the inverter is parallel-mounted to the load supply line and backs up the utility. This configuration offers a substantial cost reduction but is applicable only to low outputs, under 3 kVA, because it results in an interruption lasting up to 10 ms during transfer and does not filter inrush currents.

Inverter (on-line)

UPS configuration in which the inverter is in series mounted between the utility and the load. All power drawn by the load passes via the inverter. This is the only configuration used for high outputs.

Load (linear)

Load for which voltage form and current form are similar, or in phase. Voltage and current are related by Ohm's law U(t) = Z x I(t).

Load (non-linear)

Load (generally with a switched-mode power supply) generating major harmonic currents. Current wave form is out of phase with the voltage wave form. Ohm's law is not applicable. It can be used only with each harmonic.

Load power

Apparent power Pu that the UPS inverter supplies under given load conditions. It is less than or equal to the rated output Pn. The ratio Pu/Pn defines the % load of the inverter.

Maintenance Bypass (Wrap Around)

Manually operated series of circuit breakers creating a make before break (preferably) parallel path around the UPS and static switch. Once energized, all load power is supplied through the bypass, and the UPS can be completely de-energized allowing any service activity. Micro-outage (or micro-interruption) Total loss in the supply of power for 10 ms.

MTBF (Mean Time Between Failures)

Mathematical calculation of the duration of normal operation of a repairable device between failures. The product, expressed in hours, is an indication on the reliability of the device.

MTTF (Mean Time To Failure)

Mathematical calculation of the duration of normal operation of a non-reparable device, i.e. for which a MTBF is not possible. The product, expressed in hours, is an indication on the reliability of the device.

MTTR (Mean Time To Repair)

Mathematical calculation (or statistical average if available) of the time required to repair a device.

Noise level

Acoustical decibel level of a source of noise, measured according to the applicable ISO standard.

Non-linear load

Load (generally with a switched-mode power supply) generating major harmonic currents. Current wave form is out of phase with the voltage wave form. Ohm's law is not applicable. It can be used only with each harmonic.

Off-line inverter (or stand-by)

UPS configuration in which the inverter is parallel-mounted to the load supply line and backs up the utility. This configuration offers a substantial cost reduction but is applicable only to low outputs, under 3 kVA, because it results in an interruption lasting up to 10 ms during transfer and does not filter inrush currents.

On-line inverter

UPS configuration in which the inverter is in series mounted between the utility and the load. All power drawn by the load passes via the inverter. This is the only configuration used for high outputs.

Output (rated)

Apparent power Pn that the UPS can deliver under given load conditions (power factor = 0.8).

Overall distortion

Ratio between the rms value of all harmonics of a non-sinusoidal alternating periodic value and that of the fundamental. This value may also be expressed as a function of the individual distortion of each harmonic Hn = Yn /Y1

Percent load

Ratio between the power Pu drawn by the load and the rated output Pn of a UPS system (Pu/Pn). Sometimes referred to as the load factor.

Phase-shift filter

Filter used to reduce, if necessary, the overall distortion due to the current harmonics injected into the utility upstream of a UPS by its rectifier-charger. Filtering is superior to that of a traditional filter of the L or C type.

Power factor (l)

Ratio between the active power(true power) P supplied to a load and the apparent power S supplied to said load by an AC power supply.

For more information, please visit hbcy.

Power source (alternate)

Backup source used in the event of a mains failure. The connection time and the duration of the source depend on the type of source used.

Power source (safety)

Power source for loads defined as critical by applicable safety regulations. This supply must not be affected by a mains failure and is generally separate from other supplies.

PWM (Pulse Width Modulation)

Inverter high-frequency chopping technique using a means of regulation enabling rapid modification of pulse widths over a single period, thus making it possible to maintain the inverter output within tolerances even for non-linear loads.

Rated output

Apparent power Pn that the UPS can deliver under given load conditions (power factor = 0.8).

Reactance (sub transient Uscx %, for generator)

Relative measurement (%) of the internal impedance of an AC generator during harmonic phenomena. This reactance, also called the longitudinal sub transient reactance of the generator, is sometimes identified as X"d. For most common generators, the value ranges between 15 and 20%. It can drop to 12% for optimized systems and to 6% for special devices.

Recombination battery

Battery with a gas recombination rate at least equal to 95%, i.e. no water need be added over battery life. So, usually called "maintenance free."

Rectifier/charger

UPS component that draws on the mains the power required to supply the inverter and to float charge or recharge the battery. The alternating input current is rectified and then distributed to the inverter and the battery.

Redundancy (active)

Parallel UPS configuration in which several UPS units with equal outputs are parallel connected and share the load. In the event one UPS unit fails, the other units pick up its share without any interruption in the supply of power to the load.

Redundancy (standby)

UPS configuration in which one or several UPS units operate on stand-by, with no load or only a partial load, and can immediately back up a faulty UPS unit by no-break transfer of the load, carried out by a static switch.

Reliability

Probability that a device will accomplish a required function under given conditions over a given period of time. Rms value of AC current with harmonics The rms value Yrms of a non-sinusoidal alternating current may be determined on the basis of the individual harmonic currents: where Y is the rms value of the fundamental.

RS232C (Recommended standard RS232C)

Standard defining the communication circuits between devices for synchronous and asynchronous transmissions on the following types of lines: two-wire, four-wire, point-to-point, lines and local links with short cables. Though the standard covers only transmissions over distances up to 15 meters, it is often possible to ensure correct transmission over greater distances using high-quality shielded cable in a reasonably satisfactory electrical environment. Most terminals and devices on the market can implement this transmission standard.

RS422A (Recommended standard RS422A)

Standard RS232C is sufficient for transmissions in a normal environment. For transmissions in a disturbed environment or over long distances, standard RS422A offers a differential operation option, with a balanced voltage, ensuring far superior performance. What is more, it can be used for multipoint links, with generally up to ten connection points (one sender and up to ten receivers).

RS485 (Recommended standard RS485)

This standard is similar to RS422A except that the number of possible links is greater and up to 32 senders may be interconnected to as many receivers. This system is particularly designed for local-area networks.

Safety installation

Installation supplying electrical equipment which may have a direct effect on the safety of users and must therefore remain energized even in the event of a mains failure. In general, characteristics concerning the power supply and conditions for transfer to the safety source for such electrical equipment are covered by applicable regulations.

Safety power source

Power source for loads defined as critical by applicable safety regulations. This supply must not be affected by a mains failure and is generally separate from other supplies.

Static bypass switch

Power-electronics device that can be used to switch from one source to another without interruption in the supply of power. In a UPS, transfer is from Mains 1 to Mains 2 and back. Transfer without interruption is possible due to the fact that there are no mechanical parts and the ultra-fast switching capabilities of the electronic components.

Sub transient reactance of generator (Uscx %)

Relative measurement (%) of the internal impedance of an AC generator during harmonic phenomena. This reactance, also called the longitudinal sub transient reactance of the generator, is sometimes identified as X"d. For most common generators, the value ranges between 15 and 20%. It can drop to 12% for optimized systems and to 6% for special devices.

Thermal Runaway

Thermal runaway occurs in a VRLA battery when the rate of internal heat generation exceeds the rate at which the heat can be dissipated into the environment. It is typically triggered by excessive charge voltage, or high ambient temperatures. As temperature rises, internal current rises, resulting in higher internal temperatures, and a self-sustaining run away cycle. Should this condition continue for an extended period, the VRLA battery temperature could increase until ultimately the cells will dry-out and the container, if plastic, may soften (100°C), rupture and melt (160°C).Thermal runaway is a dangerous condition that can cause damage to property, fire and harm to personnel.

Thevenin generator

For a given load, it is possible to consider the power supply as a voltage generator, referred to as a Thevenin generator, made up of a perfect voltage Uo generator, in series with an internal impedance Zs: n Uo is the voltage measured across the load terminals, given that the load is to be disconnected (load terminals forming an open circuit), n Zs is the equivalent impedance as seen from the load terminals (again considered an open circuit), obtained by short-circuiting the upstream voltage generator(s).

Tolerance in %

Limit for allowable variations for a given quantity, expressed as a percent of the rated value.

Transformer short-circuit voltage (Uscx %)

Relative measurement (%) of the internal impedance of a transformer. This short-circuit impedance is commonly called the short-circuit voltage because it is measured during a short-circuit test (shorted secondary winding subjected to a current set to In). For most common three-phase transformers, this value ranges between 3 and 6%.

UL

Underwriters Laboratories (UL) is a non-governmental, non-profit certification organization in the United States in which not only government authorities are represented, but also consumer groups, "export" services, research, etc. Following certification, a product may bear the UL label.

UPS (Uninterruptible Power supply)

An electrical device providing an interface between the mains power supply and sensitive loads (computer systems, instrumentation, etc.). The UPS supplies sinusoidal AC power free of disturbances and within strict amplitude and frequency tolerances. It is generally made up of a rectifier/charger and an inverter together with a battery for backup power in the event of a mains failure.

UPS (parallel with redundancy)

A UPS made up of several parallel-connected UPS units with equal output ratings (P) and each equipped with its battery. If one unit fails, one or several of the others pick up the resulting excess load. If a UPS has a rated output n x P and is made up of n + k units, k is the level of redundancy for the entire set of n + k units.

UPS (parallel without redundancy)

A UPS made up of several (n) parallel-connected UPS units with equal output ratings (P) and each equipped with its battery, for large loads. The total output is equal to the number of units multiplied by their individual output (n x P). In this configuration, no UPS unit is redundant.

UPS (single)

A UPS made up of one single UPS unit (rectifier/charger, inverter and bypass) and a battery.

Vented battery

The battery cells are equipped with a filling port for distilled, demineralized water used to top up the free electrolyte.

Voltage (float)

DC voltage applied to the battery to maintain its charge level. This voltage depends on the type of battery, the number of cells and the manufacturers recommendations.

Voltage Harmonics

All alternating current which is not absolutely sinusoidal is made up of a fundamental and a certain number of current harmonics which are the cause of its deformation (distortion) when compared to the theoretical sine-wave. For each current harmonic of order n and an rms value In, there is a voltage harmonic with an rms value Un. If Zsn is the voltage source output impedance for the harmonic of the nth order, then: Un = Zsn x In

The Differences Between UPS Systems & Generators

Introduction

The world of power supply, generation and protection can be confusing &#; especially for those not in the industry. Here at Dale, we understand how frustrating and confusing it can be to get your head around certain things &#; such as the precise difference between a UPS system and generators themselves. That&#;s why we&#;ve created this quick guide to help add a bit more clarity to the picture for those looking to invest in protected power supply.

Our team works with clients across manufacturing, healthcare, finance and government and more in order to protect their computer systems, critical power equipment and power supply. Businesses need to protect themselves from power blackouts, whether they are caused by a system failure, extreme weather or anything else. The fact is that an incident like this is more than just an inconvenience &#; it puts your data, computers and equipment at a huge risk of damage and failure.

There are two main ways in which we have helped clients across a broad range of industries with protecting their power: UPS systems and generators. Both provide an excellent option for backup power supply, but we often find ourselves talking to clients who are a little confused as to the precise difference.

Each has their benefits and drawbacks, and each works in similar but slightly different ways. With this in mind, let&#;s take a look at the main differences between UPS systems and generators.

Understanding what exactly power generators and UPS systems

Before you can really appreciate the difference between these two great options for power protection from a power outage, it&#;s important to understand exactly what each of them can do and how they function.

What are generators and how do they work?

Simply put, a generator is a machine that converts mechanical energy into electrical power in order to power your business. The electricity that generators produce is used for a wide range of different uses, such as mains power supply, AC mains (alternating current) power supply, and more.

The source of the mechanical energy (motive power) can include things such as renewable sources such as hydropower and wind turbines. Here at Dale, we work in sustainable and renewable power sources every day &#; but we also provide diesel generators too. A diesel generator uses both a diesel engine and an electric generator in order to generate power.

Compared to other types of generators, the key differences for diesel generators is that they are compression-ignition engines that can use a number of different fuel types to operate. This makes them quite a flexible option and can suit your business location and configuration, running on natural gas or other liquid fuels if need be.

Diesel generators work independently and can therefore function without being connected to a power grid. This makes them an excellent option for emergency power supply in the event of a grid power failure. They can also provide backup and standby power feeding utility grids for those peak or emergency periods.

The commonly used name for the combination of a diesel engine, generator and other additional devices is a &#;diesel generator set&#; &#; often shortened to just &#;genset&#;. Other ancillary devices that might be part of a genset include control systems, jacket water heaters and circuit breakers.

What is a UPS (uninterrupted power supply) and how does it work? 

UPS is the commonly used name for uninterruptible power supply. This is a piece of equipment that provides your business and site with backup power in the short term when your mains power supply fails. Sometimes known as a battery backup, a UPS system is there to provide exactly what it says &#; uninterrupted power supply in the event of a power failure or voltage dropping to an unacceptable level. Uninterruptible power systems ensure that your devices remain protected in the event of a blackout &#; ensuring that they stay up and running despite a mains failure.

Uninterruptible power supply backup is most commonly found in IT, where data loss is a huge concern. But the fact is that uninterruptible power supply systems are applicable across all sectors because they protect and secure computers and other electronic devices with the power they need to survive a loss of mains power supply. A UPS system means that all important equipment is delivered a sufficient amount of backup power to be able to save important data and shut down safely in the event of an outage.

Unlike generators, uninterruptible power supplies are always delivered as a strictly short term standby power solution. UPS systems are designed to provide short term battery backup that lasts generally between 10 to 15 minutes as a maximum. It&#;s worth noting that much longer term options are available, but this is a key feature of most UPS systems.

Summary

As you can already tell, both generators and UPS systems provide backup to your primary power source. They help to protect your devices and electronics from damage and data loss in the event of a power outage. Let&#;s take a look at some of the most important ways in which the two solutions differ:

  • UPS is an almost instant battery backup that prevents your devices and power from being interrupted, while generators have a longer start up time.

  • Generators provide a much longer lasting backup power supply and can sustain your business for much longer than a UPS.

  • UPS systems power on automatically in the event of an outage, whereas generators need to be manually turned on.

  • The power supply for a UPS comes from AC mains, whereas generators convert mechanical energy into its own power.

  • UPS systems produce zero carbon emissions making them more environmentally friendly. Generators most often run on diesel, natural gas or other liquid fuels.

  • UPS systems are entirely noiseless, while generators can be very noisy. There are however soundproof versions and upgrades available.

  • UPS also requires no maintenance, while generators will always require some maintenance.

  • UPS are a cheaper alternative to generators.

    If you want to learn more, please visit our website ups power.